Description
Functions Phase rotation (Clockwise or Counter Clockwise),
Presence of open phase
Detection method Electrostatic induction
Measuring voltage range From 70 to 1000V AC phase to phase (sine wave, continuous input)
Clamp diameter range From Ø2.4 to 30mm insulated cables
Measuring frequency range 45 to 66Hz
Phase rotation Clockwise:
Green arrow LEDs "rotate" in clockwise, Green symbol "CW" lits, Intermittent buzzer
Counter Clockwise:
Red arrow LEDs "rotate" in counter clockwise, Red symbol "CCW" lits, continuous buzzer
Visual indication Via LEDs with Super brightness function
Battery voltage warning Power LED blinks if battery voltage is too low.
Test leads Double insulated cables, length approx. 70cm
Colours code L1(U): RedL2(V): WhiteL3(W): Blue
Applicable standards IEC 61010-1 CAT IV 600V, CAT III 1000V Pollution degree2,
IEC 61326-1, IEC 61557-1, -7
Operating temperature & humidity range Temperature/Humidity Ranges -10 to 50ºC, 80% (no condensation)
Storage temperature & humidity range Temperature/Humidity Ranges -20 to 60ºC, 80% (no condensation)
Power supply (DC battery) LR6(AA)(1.5V) ×4
* Continuous use: Approx. 100 hours (Auto power off in about 10 min. )
Dimensions 112(L) × 61(W) × 36(D) mm
Weight 380g approx.
Included Accessories 9096 (Carrying case), LR6(AA) × 4, Instruction manual